Dados Técnicos para JEHSCU-CM3

JEHSCU0360CM3 JEHSCU0200CM3 JEHSCU0250CM3 JEHSCU0300CM3 JEHSCU0350CM3 JEHSCU0400CM3 JEHSCU0500CM3 JEHSCU0600CM3 JEHSCU0680CM3 JEHSCU1000CM3 JEHSCU0800CM3
Potência frigorífica Temperatura média R-134a Nome kW 3.80 2.24     3.48 4.37 5.24 (1)     10.75 8.21
    R-404A Nome kW 6.32 3.71 4.50 5.24 5.50 7.17 8.03 (1) 10.20 10.95 17.75 13.85
    R-407A Nom kW 5.77 3.45 4.05 4.69   6.76 8.03 (1) 9.54 10.70   12.95
    R-407F Nom kW 5.73 3.33 3.94 4.58   6.75 7.99 (1) 9.59     12.90
Potência nominal Temperatura média R-134a Nom kW 1.61 1.03     1.68 1.85 2.300 (1)     4.86 3.74
    R-404A Nom kW 2.88 1.70 2.04 2.52 3.04 3.33 4.390 (1) 4.92 5.53 8.62 5.96
    R-407A Nom kW 2.58 1.63 2.04 2.45   2.97 3.930 (1) 4.65 5.54   6.24
    R-407F Nom kW 2.91 1.78 2.16 2.71   3.21 4.360 (1) 5.03     6.13
COP Medium temperature R-134a   2.36 2.19     2.08 2.36 2.28 (1)     2.21 2.20
    R-404A   2.19 2.19 2.21 2.08 1.81 2.15 1.83 (1) 2.07 1.98 2.06 2.32
    R-407A   2.24 2.12 1.99 1.92   2.28 2.04 (1) 2.05 1.93   2.08
    R-407F   1.97 1.88 1.83 1.69   2.10 1.83 (1) 1.91     2.10
Consumo anual de eletricidade Q R-134a Te -10°C kWh/a             11,969.00     19,586 16,257
  R-404A Te -10°C kWh/a 10,719     10,396 12,939 12,578 18,673.00 19,387 21,075 33,116 24,409
  R-407A Te -10°C kWh/a 10,187         10,973 17,546.00 18,408 22,240   25,491
  R-407F Te -10°C kWh/a 10,933         11,873 18,883.00 18,903     26,882
Relação de desempenho energético sazonal SEPR R-134a Te -10°C             2.69     3.37 3.10
  R-404A Te -10°C   3.62     3.10 2.61 3.50 2.64 3.23 3.19 3.30 3.49
  R-407A Te -10°C   3.48         3.79 2.81 3.19 2.96   3.12
  R-407F Te -10°C   3.22         3.49 2.60 3.12     2.95
Parâmetros em plena carga e temp. amb. 32°C (Ponto A) R-134a Te -10°C Capacidade de arrefecimento nominal (PA) kW 3.80 2.24     3.48 4.37 5.24     10.75 8.21
      Potência absorvida nominal (DA) kW 1.61 1.03     1.68 1.85 2.30     4.86 3.74
      COP nominal (COPA)   2.36 2.19     2.08 2.36 2.28     2.21 2.20
  R-404A Te -10°C Capacidade de arrefecimento nominal (PA) kW 6.32 3.71   5.24 5.50 7.17 8.03 10.20 10.95 17.75 13.85
      Potência absorvida nominal (DA) kW 2.88 1.70   2.52 3.04 3.33 4.39 4.92 5.53 8.62 5.96
      COP nominal (COPA)   2.19 2.19   2.08 1.81 2.15 1.83 2.07 1.98 2.06 2.32
  R-407A Te -10°C Capacidade de arrefecimento nominal (PA) kW 5.77 3.45   4.69   6.76 8.03 9.54 10.70   12.95
      Potência absorvida nominal (DA) kW 2.58 1.63   2.45   2.97 3.93 4.65 5.54   6.24
      COP nominal (COPA)   2.24 2.12   1.92   2.28 2.04 2.05 1.93   2.08
  R-407F Te -10°C Capacidade de arrefecimento nominal (PA) kW 5.73 3.33   4.58   6.75 7.99 9.59     12.90
      Potência absorvida nominal (DA) kW 2.91 1.78   2.71   3.21 4.36 5.03     6.13
      COP nominal (COPA)   1.97 1.88   1.69   2.10 1.83 1.91     2.10
Parâmetros em plena carga e temp. amb. 25°C R-134a Te -10°C Capacidade de arrefecimento (P2) kW 4.06 2.38     3.71 4.70          
      Potência absorvida (D2) kW 1.42 0.91     1.51 1.62          
      COP declarado (COP2)   2.86 2.62     2.46 2.90          
  R-404A Te -10°C Capacidade de arrefecimento (P2) kW   3.97 4.77                
      Potência absorvida (D2) kW   1.54 1.87                
      COP declarado (COP2)   2.58                  
  R-407A Te -10°C Capacidade de arrefecimento (P2) kW   3.69 4.31 5.00              
      Potência absorvida (D2) kW   1.45 1.83 2.22              
      COP declarado (COP2)   2.55   2.26              
  R-407F Te -10°C Capacidade de arrefecimento (P2) kW   3.64 4.31 5.06              
      Potência absorvida (D2) kW   1.53 1.89 2.37              
      COP declarado (COP2)   2.39   2.14              
Parâmetros em plena carga e temp. ambiente 43°C R-134a Te -10°C Capacidade de arrefecimento (P3) kW         3.06   4.51     9.46 7.26
      Potência absorvida (D3) kW         2.02   2.89     5.92 4.56
      COP declarado (COP3)         1.52   1.56     1.60 1.59
  R-404A Te -10°C Capacidade de arrefecimento (P3) kW 5.21 3.00 3.76 4.37 4.26 5.89 6.30 8.49 9.13 14.15 11.45
      Potência absorvida (D3) kW 3.60 2.19 2.52 3.10 3.83 4.16 5.48 6.00 6.72 10.75 7.09
      COP declarado (COP3)   1.45 1.37   1.41 1.11 1.42 1.15 1.42 1.36 1.32 1.61
  R-407A Te -10°C Capacidade de arrefecimento (P3) kW             6.77        
      Potência absorvida (D3) kW             4.86        
      COP declarado (COP3)             1.39        
Casing Cor   Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro Cinzento-claro
Dimensões Unidade Altura mm 872 662 662 662 662 872 872 872 872 1,727 1,727
    Largura mm 1,353 1,101 1,101 1,101 1,101 1,353 1,353 1,353 1,353 1,348 1,348
    Profundidade mm 575 444 444 444 444 575 575 575 575 641 641
Peso Unidade kg 112 70 72 74 74 119 123 125 126 226 222
Fan Type   Axial Axial Axial Axial Axial Axial Axial Axial Axial Axial Axial
Limite de funcionamento Temperatura ambiente Máx. °C             43        
    Mín. °C             -20        
Fluido frigorigéneo Tipo   R-134a R-134a R-404A R-404A R-134a R-134a R-134a R-404A R-404A R-134a R-134a
  Type 2   R-404A R-404A R-407A R-407A R-404A R-404A R-404A R-407A R-407A R-404A R-404A
  Tipo 3   R-407A R-407A R-407F R-407F   R-407A R-407A R-407F R-407H R448A R-407A
  Tipo 4   R-407F R-407F R-407H R-407H   R-407F R-407F R-407H R-448A R-449A R-407F
  Tipo 5   R-407H R-407H R-448A R-448A   R-407H   R-448A R-449A   R-407H
  GWP   1,430 1,430 3,922 3,922 1,430.0 1,430 1,430.0 3,922 3,922 1,430 1,430
  PAG Tipo 2   3,922 3,922 2,107 2,107 3,921.6 3,922 3,921.6 2,107 2,107 3,922 3,922
  PAG Tipo 3   2,107 2,107 1,825 1,825   2,107 2,107.0 1,825 1,495.0 1,387 2,107
  PAG Tipo 4   1,825 1,825 1,495.0 1,495.0   1,825 1,825.0 1,495.0 1,387 1,397 1,825
  PAG Tipo 5   1,495 1,495.0 1,387 1,387   1,495.0   1,387 1,397.0   1,495
Alimentação eléctrica Fase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequência Hz 50 50 50 50 50 50 50 50 50 50 50
  Tensão V 400 400 400 400 400 400 400 400 400 400 400
Notas (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - Consulte a condição: Temperatura ambiente exterior = 32°C, Temperatura de evaporação = -10°C e 10K superaquecimento (aplicação de temperatura média) (1) - SRG 20°C, Ta=32°C, Te=-35°C Consulte a condição: Temperatura ambiente exterior = 32°C, Temperatura de evaporação = -10°C e 10K superaquecimento (aplicação de temperatura média) (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - SRG 20°C, Ta=32°C, Te=-35°C (1) - SRG 20°C, Ta=32°C, Te=-35°C
  (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica (2) - O nível de pressão sonora é medida a 10m numa divisão anecoica
  (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa (3) - O seu funcionamento assenta em gases fluorados com efeito de estufa
  (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H   (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H   (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H   (4) - Dados publicados com base nas condições - Temperatura do gás de retorno de 20 °C, exceto para R-407H
  (5) - Dados publicados com base nas condições - SH10K para R-407H (5) - Dados publicados com base nas condições - SH10K para R-407H (5) - Dados publicados com base nas condições - SH10K para R-407H (5) - Dados publicados com base nas condições - SH10K para R-407H   (5) - Dados publicados com base nas condições - SH10K para R-407H   (5) - Dados publicados com base nas condições - SH10K para R-407H (5) - Dados publicados com base nas condições - SH10K para R-407H   (5) - Dados publicados com base nas condições - SH10K para R-407H