Dados Técnicos para EWFH-TZPSD

EWFH225TZPSD1 EWFH265TZPSD1 EWFH295TZPSD1 EWFH340TZPSD1 EWFH395TZPSD1 EWFH420TZPSD1 EWFH490TZPSD1 EWFH500TZPSD2 EWFH545TZPSD1 EWFH615TZPSD2 EWFH645TZPSD2 EWFH845TZPSD2 EWFH900TZPSD2 EWFH960TZPSD2 EWFHC10TZPSD2 EWFHH10TZPSD2 EWFHH11TZPSD2 EWFHC12TZPSD2
Capacidade de arrefecimento Nom. kW 314.39 377.84 413.94 481.12 545.38 672.02 716.4 762.26 709.3 901.97 965.07 1,227.87 1,313.47 1,373.69 1,471.78 1,527.41 1,605.75 588.19
Controlo de capacidade Método   Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua Variação contínua
Controlo da capacidade Capacidade mínima % 21.5 19 16.5 27.5 23 21.5 19 10 30 15 13.5 10.5 10 10 10 10 13.5 13.5
Potência nominal Arrefecimento Nom. kW 66.38 77.51 89.54 93.35 114.38 148.22 142.4 153.37 142.95 186.01 209.12 274.14 293.71 318.72 343.47 314.15 328.91 123.39
EER 4.736 4.875 4.623 5.154 4.768 4.534 5.031 4.97 4.962 4.849 4.615 4.479 4.472 4.31 4.285 4.862 4.882 4.767
IPLV 6.738 6.736 6.579 7.506 7.214 7.271 7.135 6.819 6.73 7.347 7.226 7.143 6.966 6.615 6.787 6.825 6.965 7.041
SEER 6.008 6.095 6.081 6.58 6.397 6.579 6.481 6.199 5.753 6.646 6.55 6.506 6.388 5.929 6.3 5.568 6.031 6.095
Dimensões Unidade Profundidade mm 3640 4720 4720 5800 5800 6880 6880 6880 6880 7960 7960 10120 10120 11200 11200 12280 12280 13360
    Altura mm 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553
    Largura mm 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238
Peso Peso em funcionamento kg 3628 4254 4259 5,223.1 5,233.1 5,813.1 5,939.3 6391 6,618.3 7900 7905 9329 9339 11225 11235 11797 12476 13061
  Unidade kg 3307 3846 3846 4720 4720 5229 5315 5336 5984 6358 6358 7519 7519 8341 8341 8892 9561 10070
Envolvente Cor   Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim Branco marfim
  Material   Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado Folha de aço galvanizado e pintado
Permutador de calor da água - evaporador Tipo   Chapa forjada Chapa forjada Chapa forjada Chapa forjada Chapa forjada Chapa forjada Chapa forjada Armação e tubo Chapa forjada Armação e tubo Armação e tubo Armação e tubo Armação e tubo Armação e tubo Armação e tubo Armação e tubo Armação e tubo Armação e tubo
  Volume de água l 40 48 48 58.1 58.1 58.1 76.3 289 76.3 492 492 546 546 1043 1043 1011 1011 1011
Evaporador Perda de carga de água Arrefecimento Nom. kPa 7.09 8.03 9.6 11.36 14.61 12.86 14.59 17.06 14.92 23.78 26.91 39.55 23.02 24.93 19.69 20.93 22.71 16.96
Permutador de ar Tipo   Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal
Ventilador Quantidade   6 8 8 10 10 12 12 12 12 14 14 18 18 20 20 22 22 24
  Tipo   Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa Hélice directa
  Caudal de ar Arrefecimento Nom. l/s 33765 45020 45020 56275 56275 67530 67530 67530 67530 78785 78785 101295 101295 112550 112550 123805 123805 135060
Motor do ventilador Acionamento   Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova Sem escova
Compressor Quantidade   1 1 1 1 1 1 1 2 1 2 2 2 2 2 2 2 2 2
  Tipo   Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso Compressor de parafuso
Limite de funcionamento Lado do ar Arrefecimento Mín. ° CBs -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
      Máx. ° CBs 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46
Limites de funcionamento Lado da água Evaporador Mín. ° CBs 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
      Máx. ° CBs 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
Nível de potência sonora Arrefecimento Nom. dBA 97.48 98.1 102.57 95.74 98.68 100.06 104.55 100.6 98.99 96.61 97.51 102.3 104.16 106.51 106.87 105.5 102.36 102.82
Nível de pressão sonora Arrefecimento Nom. dBA 77.74 77.83 82.3 75 77.94 78.89 83.39 79.43 77.82 75.06 75.95 80.05 81.92 83.96 84.32 82.67 79.52 79.71
Fluido frigorigéneo Tipo   R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze)
  GWP   7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7
  Carga kg 30 35 40 45 55 60 65 70 75 85 90 115 125 130 140 150 160 170
  Circuitos Quantidade   1 1 1 1 1 1 1 2 1 2 2 2 2 2 2 2 2 2
Ligações de tubagens Entrada/saída da água do evaporador (DE)   88.9 88.9 88.9 139.7 139.7 139.7 139.7 168.3 139.7 219.1 219.1 219.1 219.1 273 273 273 273 273
Alimentação elétrica Fase   3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Alimentação eléctrica Frequência Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Tensão V 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
  Limite de tensão Mín. % -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    Máx. % 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Unidade Corrente inicial Máx. A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
  Corrente ativa Máx. A 183 214 235 258 301 330 367 375 425 432 458 609 647 694 731 779 875 923
  Corrente máxima da unidade para medição dos fios A 201 235 258 283 331 363 404 412 467 476 503 670 712 764 804 857 962 1015
Notas (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol
  (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187
  (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1
  (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow.
  (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition
  (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C
  (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%.